HEPA-filtered Air Exhaust Unit for Infection Control

A simplified negative pressure generator for infection control in patients'rooms.

Features

  • It can also be used in waiting rooms or nursing homes without negative pressure if an optional circulation blower is attached.
  • A patients’ room can be remodeled to prevent air-borne infection by installing NEU-10 with an outside exhaust duct/fan system.
  • The HEPA filter is equipped for air exhaust.
  • No need for special electrical work since household electric power supply fulfills the necessary power capacity.
  • The operation mileage recorder helps maintenance of the HEPA filter.

Note: NEU-10 exhausts indoor air to the outside through an optional duct system and maintains the room at negative pressure.
When NEU-10 is installed in a standard patients’ room (W3,600mm x D6,000mm x H2,500mm), it ventilates 13.3 times per hour,
which meets the requirements of CDC guidelines regarding prevention of airborne infection.

Specifications

Model NEU-10
Version Exhausting air outside the room

Returning air to the room

Dimensions (W × D × H) (㎜) 750 × 400 × 1,550 750 × 400 × 1,755
Filter HEPA filter (Dust collect efficiency: PAO particles of 0.3μm 99.99% or higher)
Pre-filter(Antimicrobial PP honeycomb net)
Air volume flow rate High: 10. 5 m3/min  Low: 5.3 m3/min High: 11 m3/min  Low: 5.5 m3/min
Noise High: 52 dB(A)  Low: 38 dB(A) Hight: 53 dB(A)  Low: 40 dB(A)
Material Steel plate with resin coating (antibacterial coating)
Power consumption High: 115 W      Low: 25 W
Weight About 75 kg About 80 kg
Power requirement Single phase 100 V  50/60 Hz